Why do my kitchen sockets trip when I turn the cooker on?
Here are the usual causes, most likely first, and how an electrician would track it down.
Likely causes
- Earth leakage from a cooker element (damp/failed element) adding to leakage already on the same RCD
- cooker and kitchen sockets sharing one RCD, so normal leakage adds up
- A neutral-earth fault on the cooker circuit
- Moisture in the cooker outlet or connection
How you'd find it
- Safe isolation, then IR test the cooker circuit and appliance: L+N to E at 500 V – expect ≥ 1 MΩ; an element under that is suspect
- Split the loads: run the cooker with the sockets unplugged to see which side leaks
- N–E test on each circuit to find borrowed neutrals
Usual fix
Replace the leaky element or cooker; fix any N–E fault; if leakage is spread, split circuits over more RCDs/RCBOs.
⚠️ Safety: Stop and safely isolate before touching anything. If you're not qualified, leave it to a Safe Electric Registered Electrical Contractor.
Regulation: I.S. 10101 411.3.3 (RCD protection); IR test Part 6.